UV2 Series

Images

  • UV2 Series
UV2 Series

Type and meaning

UV2- M motor breaker having thermomagnetic protection

The standard rated power of three –
phase motor (kW)
Heating trip setting range (A)Magnetic trip current (A)1 the current when having outer cover (A)Model (button control)Weight (kg)
230V400V415V440VId±20%
 – – – –0,1…….0,161,50,16UV2-M01C0,260
 0,16…….0,252,40,25UV2-M02C0,260
 – 0,25…….0,405 0,40UV2-M03C0,260
 0,40…….0,6380,63UV2-M04C0,260
0,370,63…….1131UV2-M05C0,260
0,370,551…….1,622,51,6UV2-M06C0,260
0,370,750,751,1 1,6…….2,533,52,5UV2-M07C0,260
0,751,51,51,52,5…….4514UV2-M08C0,260
1,12,22,234…….6,3786,3UV2-M10C0,260
2,24446…….101389UV2-M14C0,260
35,55,57,59…….1417013UV2-M16C0,260
47,59913…….1822317UV2-M20C0,260
5,511111117…….2332721UV2-M21C0,260
5,511111120…….2532723UV2-M22C0,260
7,515151524…….3241624UV2-M32C0,260

UV2- RS motor breaker having thermomagnetic protection

The standard rated power of three –
phase motor (kW)
Heating trip setting range (A)Magnetic trip current (A)Model (button control)Weight (kg)
230V400V415V440VId±20%
 – – – –0,1…….0,161,5UV2-RS01C0,260
  –  –  –  –0,16…….0,252,4UV2-RS02C0,260
 – – – –0,25…….0,405UV2-RS03C0,260
 – – – –0,40…….0,638UV2-RS04C0,260
 – – –0,370,63…….113UV2-RS05C0,260
 – 0,37 –0,551…….1,622,5 UV2-RS06C0,260
 0,37 0,75 0,751,1 1,6…….2,533,5 UV2-RS07C0,260
 0,75 1,5  1,51,52,5…….451 UV2-RS08C0,260
 1,1 2,2 2,234…….6,378 UV2-RS10C0,260
 2,24 446…….10138 UV2-RS14C0,260
 3  5,5 5,57,59…….14170UV2-RS16C0,260
4 7,5 9913…….18223UV2-RS20C0,260
5,511111117…….23327UV2-RS21C0,260
5,511111120…….25327UV2-RS22C0,260
7,515151524…….32416UV2-RS32C0,260

UV2- LS motor breaker having thermomagnetic protection

The standard rated power of three –
phase motor (kW)
Heating trip setting range (A) Magnetic trip current (A) 1 the current when having outer cover (A)Model (button control)Weight (kg)
230V400V415V440V Id±20%
 – – – –0,405LR2-D1303UV2-LS030,330
  –  –  –  –0,638LR2-D1304UV2-LS040,330
 – – –0,37113LR2-D1305UV2-LS050,330
0,37 –0,551,622,5LR2-D1306UV2-LS06C0,330
0,370,75 0,751,12,533,5LR2-D1307UV2-LS07C0,330
0,751,51,51,5451LR2-D1308UV2-LS08C0,330
1,12,22,2 36,378LR2-D1310UV2-LS100,330
2,244410138LR2-D1314UV2-M08C0,330
35,55,57,514170LR2-D1316UV2-LS16C0,330
47,59918223LR2-D1321UV2-LS20C0,330
5,511111123327LR2-D1322UV2-LS22C0,330

Electric trip feature

TypeUV2-AUUV2-AXUV2-AS
Rated insulation voltage (U) is in
accordance with IEC947-1
V690400690
The work voltage is in accordance
with IEC947-1
V0,85….1,1 Ue 0,7…1,1 Ue
 Discharge voltageV 0,35…0,7 Ue 0,2….0,75 Ue
 Start power – consuptionVA 12 14
W 8 10,5
 Charge power – consuptionVA 3,55
W 1,1 1,6
 Motion time is in accordance with
IEC947-1
ms from voltage achieving work value to S-GV2 being cut off 10….15
 Load coefficient 100 %
Wiringone or two leads
 Hard lead 1…2,5
 Soft lead without wiring terminalmm² 0,75…2,5
 Soft lead with wiring terminalmm² 0,75…1,5
 Tightening torsionNm 1,4 maximum

Dimension and Installation